Automatic Engine
Control Modules
From £60.00
Contact us for details
The Model 002F(K,RS) is an
Automatic Engine Control Module designed to automatically start and stop
the engine. It will indicate the operational status and fault
conditions, automatically shut down the engine and indicate the start
engine failure by a flashing LED on the front panel. Other simultaneous
faults are indicated by steady LED.
Start relay
0.5 second after the fuel
relay is energized, the 3 attempt start will begin its start sequence:
the start relay will energize, feeding battery +ve (on terminal 6) to
terminal 7 and thence on to the starter circuit. The crank period is set
for 12 seconds.If the engine has not fired by the end of 1st attempt,
the starter is turned off for a 20 sec. period. The sequence will then
repeat up to a maximum number of start attempts.
Following a successful start,
sensed when AC alternator's voltage rises above 40% of nominal, the
crank relay is de-energized and latched out to prevent reengagement of
the starter with the engine running.
Should the engine still fail
to start after the maximum number of attempts, FAIL TO START is
displayed and the starter is latched out until reset via stop position
of (rocker switch, selector switch, key switch where applicable).
Operation of the module is
via (rocker switch, selector switch, key switch) mounted on the front
panel with START and STOP positions or via remote start terminal 1.
Relay outputs are provided
for:
-
Fuel
Solenoid Output
-
Start
Output
-
DC
alternator excitation
The relays supply
positive plant supply out.
Configurable inputs are
available for:
Multiple alarm channels
are provided to monitor the following:
The AESM 002F(K,RS) series
modules have been designed for front panel mounting.
The module is fitted into the
cut-out with the fixing clips removed.
These are then fitted from
the rear.
DC Supply:
8 to 33 V Continuous.
Max. Operating Current: 90 mA
at 12 V. 87 mA at 24 V;
Max. Standby Current: 10 mA
at 12 V. 10 mA at 24 V;
Alternator Input Range: 15 -
300 V ac RMS;
Low Frequency Limit:30 Hz;
High Frequency Limit: 57Hz;
Start Relay Output:
2 Amp DC at supply voltage.
Fuel Relay Output: 2 Amp DC
at supply voltage.
Dimensions: 77 X 77 X
111mm
Operating Temperature Range:
-30 to +70°C
Other Models Available with Pre-Heater and
Auto Transfer
|